Part Number
Definition:
A UNIT COMPRISING A FIN AND TUBE HEAT TRANSFER ELEMENT, FILTERS AND MAY OR MAY NOT HAVE A MOTOR DRIVEN FAN, INCLOSED IN A CASING FOR THE PURPOSE OF COOLING AND REMOVING MOISTURE FROM THE AIR IN A SPACE WHERE THE UNIT IS INSTALLED. IT MAY INCLUDE ELECTRIC HEATER AND/OR ELECTROSTATIC PRECIPITATOR. EXCLUDES UNITS CONTAINING COMPRESSOR, CONDENSER AND MEANS FOR INTRODUCING AIR FROM OUTSIDE SOURCES.
CAGE Information
Code | Company |
---|---|
38450 | ENGINEERED COIL COMPANY DBA DRS MARL |
Federal Supply Class
Title
REFRIGERATION AND AIR CONDITIONI
Inclusions:
INCLUDES HEAT EXCHANGER EQUIPMENT; REFRIGERANT STRAINERS; REFRIGERATION COMPRESSORS; AIR CONDITIONING AND REFRIGERATION SERVICING EQUIPMENT, SUCH AS CHARGING AND TESTING MANIFOLDS, LINES AND UNITS; OPERATING COMPONENTS OF REFRIGERATION AND AIR CONDITIONING EQUIPMENT, PLANTS, AND SYSTEMS CLASSIFIED IN CLASSES 4110 AND 4120.
Exclusions:
EXCLUDES REFRIGERATION AND AIR CONDITIONING PLANTS (SEE CLASSES 4110 AND 4120): COLLECTIONS OF REFRIGERATION COMPONENTS "PACKAGED" AS A UNIT INCLUDING A REFRIGERATION COMPRESSOR, CONDENSER, EVAPORATOR, ETC., SPECIFICALLY DESIGNED AND TAILORED FOR APPLICATIONS SUCH AS WALK-IN TYPE REFRIGERATORS. INDIVIDUAL COMPONENTS OF THE "PACKAGED" UNIT WILL BE CLASSIFIED IN CLASS 4130, OR AS OTHERWISE SPECIFICALLY PRESCRIBED BY THE INDEXES AND STRUCTURE OF THE FSC. THE COMPLETE "PACKAGE" UNIT WILL BE CLASSIFIED IN CLASS 4110.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FAAZ | PHASE | THREE FAN MOTOR |
ACZV | COOLING MEDIUM | CHILLED WATER |
AWLS | CONNECTION TYPE | FLANGE UNION |
AWLW | RETURN CONNECTION SIZE | .625 IN OD |
FAAZ | PHASE | THREE HEATER |
AWMA | FAN TYPE | CENTRIFUGAL |
ABMK | OVERALL WIDTH | 39.000 INCHES NOMINAL |
AWGJ | TUBE MATERIAL | COPPER |
AWLZ | CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
AWMB | FAN DRIVE TYPE | DIRECT |
ELEC | VOLTAGE IN VOLTS | 440.0 FAN MOTOR |
FREQ | FREQUENCY IN HERTZ | 60.0 HEATER |
ELEC | VOLTAGE IN VOLTS | 440.0 HEATER |
ABFY | OVERALL DEPTH | 17.000 INCHES NOMINAL |
CWMQ | HEATER WATTAGE RATING IN KILOWATTS | 3.0 |
AWLQ | COIL TUBE QUANTITY | 1 |
CWMP | NOMINAL CAPACITY IN BTU PER HOUR | 39910.0 COOLING AND 39910.0 HEATING |
ADTV | CASE MATERIAL | STEEL, GALVANIZED |
AEQC | OPERATING SPEED AT RATED CAPACITY IN RPM | 1800.0 |
AWLT | SUPPLY CONNECTION SIZE | .625 IN OD |
AGAV | END ITEM IDENTIFICATION | FAN COIL UNIT |
FEAT | SPECIAL FEATURES | MIL-A-24775; REVERSABLE CONNECTIONS (LH/RH), HIGH IMPACT SHOCK AND VIBRATION RESISTANCE; HAS LVP (LOW VOLTAGE PROTECTION) CAPABILITY |
ABKW | OVERALL HEIGHT | 52.000 INCHES NOMINAL |
FREQ | FREQUENCY IN HERTZ | 60.0 FAN MOTOR |
AWLR | TUBE CIRCUIT QUANTITY | 32 |
ACDC | CURRENT TYPE | AC FAN MOTOR |
ACDC | CURRENT TYPE | AC HEATER |